Product features STHCPV Combined Probe - CAN
By selecting specific sensors, it is possible to choose a variant of the sensor with different combinations of measured quantities (combination of two to five measured quantities).
Combined temperature, relative humidity, CO sensor 2 , atmospheric pressure and VOC - STHCPV 104 consists of a plastic head with grooves, in which a printed circuit board with individual sensors and a converter are located to ensure communication via the CAN bus. The temperature, relative humidity, atmospheric pressure and VOCs are measured by a common internal sensor whose signal is processed in a microprocessor and converted into a CANopen output signal with CiA DS 301 specification. The CO value 2 is measured by an NDIR module whose digital signal is also converted. CANopen with CiA DS 301 specification. An auto-calibration function is available for CO concentration sensor 2 to ensure that the sensor is set to the minimum CO value 2 .corresponding to the level of external concentration. The sensors temperature, relative humidity, CO 2 , atmospheric pressure and VOC - STHCPV 104 are conform to protection class IP 30 according to the modified standard EN 60529. Pleasant design and quality materials ensure that sensors temperature, relative humidity, CO 2 , atmospheric pressure and VOC - STHCPV 104 do not disturb even in interiors subject to high aesthetic requirements. The sensors de temperature, relative humidity, CO 2 , recommended atmospheric pressure and VOC are located at a height of 1,5 m from the interior wall, in the area of movement of people, away from sunny places and affected by the temperature of the walls, heat sources or lighting.
The sensors temperature, relative humidity, CO 2 , atmospheric pressure and VOC - STHCPV 104 are designed to operate in a chemically non-aggressive environment. Operating conditions to ensure the proper functioning of the CO sensor 2 are the following:
- ambient temperature: 0 to 45 ° C
- relative humidity: 0 to 85% (non-condensing)
- atmospheric pressure: 87 to 106 kPa
Sensor type | STHCPV 104 |
Temperature measurement range ** |
0 to 45 ° C with guaranteed CO measurement accuracy 2 de |
Temperature measurement accuracy * | ± 0,5 ° C at 25 ° C ± 1,0 ° C in the range of 0 to 65 ° C |
Relative humidity measurement range * | 0 to 85% with CO measurement accuracy 2 guarantee 0 to 95% without CO measurement accuracy 2guarantee |
Relative humidity measurement accuracy * | ± 3% between 20 and 80% ± 4,5% between 0 and 19% and 81 to 95% |
CO measurement range 2 * | 400 to 5000 ppm |
CO measurement accuracy 2 * | ± 100 ppm |
CO reaction time 2 (90%) | 90 s |
VOC measurement range (IAQ index) * | 0 to 500 |
VOC measurement accuracy * | ± 15% |
Measuring range of atmospheric pressure * | 300 to 1100 hPa |
Measurement accuracy of atmospheric pressure * (in the temperature range from 0 to 65 ° C, in the range from 300 to 1100 hPa) |
absolute deviation: ± 0,6 hPa long-term temperature stability: ± 1,0 hPa |
Measurement accuracy of atmospheric pressure * (temperature range 25 to 40 ° C, range 700 to 1100 hPa) |
absolute deviation: ± 0,12 hPa |
Output signal | CAN / CANopen-CiA DS 301 |
Supply voltage | 15 to 30 V DC |
Nominal supply voltage U n | 24 V DC |
The consumption | max: 500mW typical: 300 mW |
Degree of protection | IP 30 according to EN 60529, as modified |
Head dimensions | 71,9 x 59 x 27 mm |
Head material | lexan |
The weight | min 35g |
Recommended conductor cross-section | 0,14 to 1 mm 2 |
Note: The manufacturer reserves the right to modify the design and technical characteristics of the products.
SENSOR INSTALLATION AND MAINTENANCE
The sensors are designed to be mounted on a wall or other vertical surface. For fixing, it is necessary to prepare the required holes for mounting screws using a template (supplied with the sensor).
Before connecting the power cable, it is necessary to separate the perforated cover from the plastic base. Remove the cover and insert the cable through the 9 mm hole, apply the base to the surface and screw with two screws or bolts. The length of the bolts or fixing screws for fixing should be chosen according to the thickness of the plastic base. Connect the power cable to the terminals in accordance with the “Wiring” section. Diagram: place the perforated cover on the fixed base and lock it by clicking on it. After installation and connection to the electrical measuring device, the sensor is ready for use. The sensor does not require any particular maintenance.