Pressure sensor for commercial air conditioning
Product features Pressure sensor for commercial air conditioning
Technical drawing | ![]() |
Working pressure |
0 ~ 4.6MPa (adjustable range) |
Precision |
± 1,5% FS (linear, hysteresis, repeatability) |
Full error band |
± 3,0% of full scale (-30 ° C to + 100 ° C) - Another high precision version is available |
Operating temperature |
-30°C ~ +100°C |
Storage temperature |
-40°C~+150°C |
Protection pressure |
6.9Mpa |
Burst pressure |
9.2Mpa |
Measuring fluid |
R22, R407C, R134A and other refrigerants |
Durée de vie |
5 million complete cycles |
Vibration |
11g (20~2000Hz) |
Electrical interface |
YAZAKI RK03FB |
Protection level |
IP65 |
Housing material |
copper C3602 |
Pressure connection |
7/16-20UNF-2B |
Supply voltage |
5.0±0.25VDC |
Output Voltage |
0.5 ~ 4.5VDC (adjustable in the range of 5V) |
Supply current |
10mA (max) |
Load impedance |
10KΩ |
Output response time |
3mS |
Protection contre les surtensions |
16VDC |
Reverse voltage |
-14VDC |
Protection against short circuits |
Yes |
EMC (1 MHz - 512 MHz) |
3V/m |
ESD |
Air 15KV contact 8KV terminal 2KV |