Europe: +33 2 33 61 16 70 | America: +1 438 800 6104

Connection head thermocouple with fast response time connection - ATEX intrinsically safe

Reference GXI-TTWSR / GXI-APTTWSR

Delivery in 3 to 5 weeks
  • Design temperature range: -40 .. + 800 ° C
  • Particularly suitable for steam and gas applications
    with high process pressures and temperatures
  • Installation in hazardous areas:
    Gases, vapors, mists (G): Zone 0, 1, 2
    Dust (D): Zone 20, 21, 22
    Mining: M1 

Product features Connection head thermocouple with fast response time connection - ATEX intrinsically safe

Features

  • Single and double TC
  • Interchangeable mineral insulated measuring insert
  • Installation in an external thermowell
  • ATEX cable gland I M1, II GD, IP65 (cable diameter Ø5..10mm)
  • Output signal: TC or 4..20 mA (option)


Description

The sensor consists of an interchangeable measuring insert, a cooling neck and an aluminum connection head where the mounting of a temperature transmitter with a 4-20 mA / HART® or Profibus output signal ®PA is possible.

The measuring insert is the replaceable part of the complete sensor which reduces the time and cost of maintaining the measuring device installed in the object. The spring-loaded attachment of the measuring insert provides perfect pressure at the bottom of the protection tube, reduces reaction time to temperature changes and increases measurement accuracy and reduces natural vibrations, thus avoiding mechanical and electrical faults .

The insertion length, the diameter of the measuring insert, the connection head as well as the type and number of sensors and the accuracy can be individually selected for the respective application.

Temperature transmitter (option)

The transmitter is mounted inside the sensor connection head: directly on the measuring insert or in the cap
top of the head.

The second method is advantageous because it allows to quickly change the standard measurement support without having to disassemble the transmitter; this means reduced sensor maintenance time and costs and the protection of wires from possible damage. Mounting of two transmitters inside the connection head available on request.

Type G1 Aluminum, Exe M20x1,5 cable gland, IP68
Type G2 Aluminum, Exe M20x1,5 cable gland, IP68
Type G5 Aluminum, 2 x Exe M20x1,5 cable gland, IP68
Type G6 Aluminum, 2 x Exe M20x1,5 cable gland, IP68