Wired thermocouple with intrinsically safe ATEX plunger

Reference: GXI-TTE411R / GXI-TTE412R

Wired thermocouple with intrinsically safe ATEX plunger
  • Measuring range: -40 .. + 400 ° C (depends on cable insulation)
  • Fine chemical industry
  • Light energy industry
  • General industrial services
  • Food industry
  • Installation in hazardous areas:
    Gases, vapors, mists (G): Zone 0, 1, 2
    Dust (D): Zone 20, 21, 22
    Mines: M1 

International shipping

Standard or express delivery

Secure Payments

All payments are secure and approved.

Best price guarantee

Contact us to define your payment method.

+33-233-611-670

English - French - German - Spanish

Product details about "Wired thermocouple with ATEX plunger with intrinsic safety"

Features

  • Single or double TC:
    Type J (Fe-CuNi),
    Type K (NiCr-NiAl),
    N-type (NiCrSi-NiSi),
    T-type (Cu-CuNi),
    E-type (NiCr-CuNi)
  • Stainless steel AISI321 / 1.4541 or AISI316L / 1.4404, AISI316Ti / 1.4571 on request
  • Construction type: straight or angled


Temperature difference

The temperature range of the sensor depends on the insulation of the connection cable.

image

isolation

measuring range

PVC / Sheath: PVC -10 .. + 105 ° C
Silicone / Sheath: silicone -40 .. + 180 ° C
Teflon® FEP / Sheath: silicone -40 .. + 180 ° C
Teflon® FEP / Sheath: silicone / Braid: copper -40 .. + 180 ° C
Teflon® PFA / Sheath: teflon® PFA -40 .. + 260 ° C
Teflon® FEP / Sheath: teflon® FEP / Braid: copper -40 .. + 205 ° C
Fiberglass / Sheath: fiberglass / Braid: stainless steel -40 .. + 400 ° C


Description

The thermocouples of this series are designed to be screwed directly into the process, mainly into vessels and pipelines. These thermocouples are suitable for liquid and gaseous media under moderate mechanical load and under normal chemical conditions.

Construction

The sensor consists of a thermocouple cable, a protective tube with threaded process connection and a cable.

Insertion length, process connection, construction type, thermocouple type, accuracy, cable insulation can be individually selected for the respective application.

Autres versions

This datasheet contains only a small portion of our wired thermocouple supply program. On customer request, other versions can also be delivered.

General

  • Reference GXI-TTE411R / GXI-TTE412R
  • Name Wired thermocouple with intrinsically safe ATEX plunger

Features

  • Product Type 2x Thermocouple
    Thermocouple
  • Maximum operating temperature 400°C
  • Diameter 3 mm
    4 mm
    5 mm
    6 mm
    8 mm
  • Model Wired probe
  • Thermocouple type J
    K
  • certification ATEX EXI
  • Cable length 1000 mm
    1500 mm
    2000 mm
    2500 mm

8 other products in the same category: