Thermocouple with connection head 1800 ° C ATEX intrinsically safe
- ATEX EXI
- 0 to +1800 ° C
- Single or double TC
- Terminal block
Signed sensors ATEX II 1/2G et ATEX II 1/2D have been designed for temperature measurement in all gas, liquid, mist and dust explosion zones. In zone 0 or 20 can only be a protection tube. The connection head can only be in zones 1 (21) or 2 (22). The boundary between the zones is the threaded connection.
Signed sensors ATEX II 2G et ATEX II 1/2D have been designed for temperature measurement in zones 1 (21) and 2 (22).
The sensor consists of an interchangeable measuring insert, a welded thermowell with process connection and a PR7501 temperature transmitter mounted on site.
The measuring insert is the replaceable part of the complete sensor which reduces the time and cost of maintaining the measuring device installed in the object. The spring-loaded attachment of the measuring insert provides perfect pressure at the bottom of the protection tube, reduces reaction time to temperature changes and increases measurement accuracy and reduces natural vibrations, thus avoiding mechanical and electrical faults .
Insertion length, process connection, thermowell design and material, connection head can be individually selected for the respective application.
The field mounted HART® PR7501 temperature transmitter with display and optical buttons allows easy programming, service and diagnosis from the front of the sensor. The sensor display can be rotated in 90 degree increments for easy vertical or horizontal viewing.
Image | Optical buttons |
![]() |
With |
![]() |
Without |