INDOOR CO2 SENSORS WITH 0-10 V OUTPUT

Reference GKSC700R

Sensor type KSC 700

Measuring values

CO2

0 to 10 V output signal

CO2 measurement range * 400 to 5000 ppm

CO2 measurement accuracy * ± 50 ppm *

CO2 response time (90%) 20 s

Supply voltage U 15 to 30 VDC

Nominal supply voltage Un 24 VDC

Maximum consumption: 500 mW

typical: 250 mW

Protection index IP 30 according to. according to EN 60529, as amended

Head dimension 71,9 x 59 x 27 mm

LEXAN head material (conforms to EN 45545-2, as amended)

Recommended wire cross section 0,14 to 1 mm2

Min weight 35 g

* The measuring ranges and accuracies given for the individual sensors refer to the operating conditions when the supply voltage is connected.

Tests

Shock and vibration tests category 1, class B according to EN 61373, as amended

Electromagnetic compatibility according to EN 50121-3-2, as amended

Insulation test 1,5 kVDC for 1 minute according to EN 50155, as amended

Fire resistance

according to EN 45545 (possible according to NFPA 130), as amended

Product features INDOOR CO2 SENSORS WITH 0-10 V OUTPUT

The KSC 700 - CO2 sensor with 0 to 10 V output is designed to measure the concentration of carbon dioxide in the air in areas protected from water.

The KSC 700 - CO2 sensor with CO2 output consists of a plastic ribbed head where a printed circuit board with the CO2 sensor and a converter is placed to establish communication through the voltage output 0 to 10 V. The CO2 value is measured by an NDIR module, the output signal of which is also converted to an output signal of 0 to 10 V. For the KSC 2 CO700 concentration sensor, there is an autocalibration function available to set the sensor to the value minimum CO2 corresponding to the outdoor concentration level. The KSC 700 - CO2 sensor with 0 to 10 V output meets the protection index IP 30 according to EN 60529, as amended. Appropriate design and high-quality materials ensure that the sensor is not disturbing, even in interiors with high aesthetic requirements. You can choose the color of the box white or gray.

The KSC 700 - CO2 sensor with 0 to 10 V output is designed to operate in a chemically non-aggressive environment; its use should be chosen according to the temperature and chemical resistance of the head and the individual sensors. The operating conditions to establish the correct function are:

ambient temperature near the sensor: 0 to 45 ° C

ambient relative humidity: 0 to 95% (non-condensing humidity)

atmospheric pressure: 87 to 106 kPa

TESTS, DECLARATION, CALIBRATIONS

Type tests are carried out by a notified body according to standard EN 50155, as amended, Railway applications - Electronic equipment used on rolling stock, Art. 12.2.9, 12.2.11

- Electromagnetic compatibility according to EN 50121-3-2, as amended

- Insulation test according to EN 50155, as amended

- Shock and vibration tests according to EN 61373, as amended

The product meets the parameters in accordance with EN 45545-2, as amended, Fire protection of railway vehicles - Part 2: Requirements for the fire behavior of materials and components. May be supplied with materials that meet NFPA 130 fire safety standard, as amended.