INDOOR CO2 SENSORS WITH RS 485 (MODBUS) OUTPUT KSC 102

Reference GKSC102R

Delivery in 3 to 5 weeks

Sensor type KSC 102

CO2 measurement values

CO2 measurement range * 400 to 5000 ppm

CO2 measurement accuracy * ± 200 ppm *

CO2 response time (90%) 90 s

RS 485 / MODBUS RTU output signal

Supply voltage U 15 to 30 VDC

Nominal supply voltage Un 24 VDC

Maximum consumption: 500 mW

typical: 300 mW

Protection against ingress

IP 30 according to. according to EN 60529

Head dimension 71,9 x 59 x 27 mm

LEXAN head material (conforms to EN 45545-2)

Min weight 35 g

Recommended wire cross section 0,14 to 1 mm2

* The measuring ranges and accuracies given for the individual sensors refer to the operating conditions when the supply voltage is connected.

Tests

Shock and vibration tests category 1, class B according to EN 61373

Electromagnetic compatibility according to EN 50121-3-2

Insulation test 1,5 kVDC for 1 minute according to EN 50155

Fire resistance

according to EN 45545 (possible according to NFPA 130)

Product features INDOOR CO2 SENSORS WITH RS 485 (MODBUS) OUTPUT KSC 102

The KSC 102 - CO2 sensor is designed to measure the concentration of carbon dioxide in the air in areas protected from water.

The KSC 102 - CO2 sensor consists of a plastic ribbed head where a printed circuit board with the CO2 sensor and a converter is placed to establish communication via the RS 485 bus. The CO2 value is measured by an NDIR module. whose digital signal is also converted into an output signal of MODBUS RTU. For the CO2 concentration sensor, an auto-calibration function is available to set the sensor to the minimum CO2 value corresponding to the outdoor concentration level. The KSC 102 - CO2 sensor meets the protection rating IP 30 according to EN 60529. Appropriate design and high quality material ensure that the sensor is not disturbing, even in interiors with high aesthetic requirements. You can choose the color of the box white or gray.

The KSC 102 - CO2 sensor is designed to operate in a chemically non-aggressive environment; its use should be chosen according to the temperature and chemical resistance of the head and the individual sensors. The operating conditions to establish the correct function are:

Ambient temperature near the sensor: 0 to 45 ° C

Ambient relative humidity: 0 to 95% (non-condensing humidity)

Atmospheric pressure: 87 to 106 kPa

 TESTS, DECLARATION, CALIBRATIONS

Type tests are carried out by a notified body according to standard EN 50155, as amended, Railway applications - Electronic equipment used on rolling stock, Art. 12.2.9, 12.2.11

- Electromagnetic compatibility according to EN 50121-3-2, as amended

- Insulation test according to EN 50155, as amended

- Shock and vibration tests according to EN 61373, as amended

The product meets the parameters in accordance with EN 45545-2, as amended, Fire protection of railway vehicles - Part 2: Requirements for the fire behavior of materials and components. The materials also meet the requirements of the NFPA 130 fire safety standard, as amended.