Compressed air temperature and humidity controller with 230Vac / 8A relay *Step required

AR006676
In production :  1 to 2 weeks
  • Humidistat, thermostat.
  • Two relay outputs.
  • T + RH probe in duralumin.
  • Exterior and interior.

Volume reductions

Quantity Unit price Total price
1 473,67 € 473,67 €
10 426,30 € 4 263,00 €
25 404,99 € 10 124,76 €
50 383,67 € 19 183,49 €
Unit price
473,67 €
Final price
473,67 €
Your configuration:

International shipping

FREE shipping in Europe from 100 € of purchase

Secure Payments

All payments are secure and approved.

Best price guarantee

Contact us to define your payment term.

+33-233-611-670

English - French - German - Spanish

TECHNICAL DATA

Humidity, thermostat with two relay outputs.

T + RH probe in hard anodized duralumin for compressed air up to 25 bars with 1 m of cable.

Cable lengths of 2m or 4m are available optional.

Use Case exterior and interior.

Relative humidity, temperature probe on a cable.

The measured values ​​are also converted to another interpretation of humidity: dew point temperature, absolute humidity, specific humidity, mixing ratio, specific enthalpy.

INCLUDED IN DELIVERY

  • H3061P
  • Manual
  • Traceable calibration certificate
  • Free Tsensor configuration software


MEASURED VALUES

- Temperature
- Relative humidity

Maximum switching voltage, current, power of the relay output: 250Vac, 8A

Audible alarm: from integrated acoustic signal - switchable

Relative humidity range: 0 to 100%

Accuracy of the relative humidity measurement: ± 2,5% relative humidity from 5 to 95% at 23 ° C

Accuracy of temperature output: ± 0,4 ° C from -30 to + 100 ° C
± 0,4% from reading at + 100 ° C

Available temperature units: degrees Celsius, Fahrenheit

Dew point temperature range: -60 to +80 ° C

Accuracy of dew point temperature output (for details, see instruction manual): ± 1,5 ° C for the dew point + 10 ° C and more at room temperature + 25 ° C

Dew point temperature output accuracy: ± 2,0 ° C for dew point temperature 0 ° C at room temperature + 25 ° C

Dew point temperature output accuracy: ± 3,0 ° C for dew point temperature -10 ° C at room temperature + 25 ° C

Dew point temperature output accuracy: ± 6,0 ° C for dew point temperature -20 ° C at room temperature + 25 ° C

Accuracy and absolute humidity output range: ± 1,5 g / m3 at ambient temperature T <25 ° C
range 0 to 400 g / m3

Accuracy and specific humidity flow range: ± 2g / kg at ambient temperature T <35 ° C
range 0 to 550 g / kg

Accuracy and output range of mixing ratio: ± 2g / kg at ambient temperature T <35 ° C
range 0 to 995 g / kg

Accuracy and specific enthalpy output range: ± 3kJ / kg at ambient temperature T <25 ° C
range 0 to 995 kJ / kg

Temperature range : -30 to + 80 ° C

LCD display operating temperature range: readable at operating temperature + 70 ° C, it is recommended to turn off the LCD screen above + 70 ° C

Temperature compensation of humidity sensor: the whole temperature range

Filtering capacity of the sensor cover: 0,025 mm - filter with stainless steel mesh

IP protection: Electronics IP65, sensors IP40

Power : 110 to 240 V / 50 Hz to 60 Hz

Current consumption: 230 VAC - max. 70 mA, 115 VAC - max. 120 mA

Mechanical connection of the probe: G1 / 2 with O-ring

Probe cable length: 1m, 2m or 4m optional

Dimensions: 136 x 161 x 45 mm (W x H x D), probe length 150 mm, probe diameter 18 mm

Weight: about 490g - 1m probe

Warranty: 3 years 

Information

Measured
Humidity
Product Type
regulators

Downloading

Introduction Manual

AR004558 / AR005071 / AR006674 / AR006675 / AR006676 / AR006677 / AR006678 /

Download (2.9M)

Quick Start

AR004558 / AR005071 / AR006674 / AR006675 / AR006676 / AR006677 / AR006678

Download (780.75k)
Related products (8 other products in the same category)

Create account