Product features Thermometer with Ethernet interface and relay

TECHNICAL DATA

Ethernet temperature sensor for Pt1000 sensors with two relay outputs.

The sensor is designed for online temperature monitoring.

Three binary inputs for two-state signal detection are the advantage.

The other devices are controlled by two relay outputs.

Processing and analysis of measured data:

  • Online in Cloud
  • Database software
  • Integration into third-party systems 


INCLUDED IN DELIVERY

  • AR003912
  • Manual
  • Traceable calibration certificate
  • Free Tsensor configuration software
  • Cloud for 3 months 


MEASURED VALUES

- Temperature
- Two state signal

Accuracy of temperature output: ± 0.2 ° C (Without temperature probe)

Resolution: 0.1°C

Measuring interval: 2s

Available units: Degrees Celsius, Fahrenheit

Temperature operating range: -30 to + 80 ° C

Protection sign : IP40

Number of relay outputs: 2

Maximum power of the voltage and current relay: 50V, 2A, 60VA

Number of binary inputs: 3

Signal for binary inputs: From voltage free contact, open collector or two state voltage signal.
The inputs are not galvanically isolated.

Minimum pulse duration at binary input: 500ms

low voltage at binary input: 0 to + 0.5V

high voltage at binary input: +3.0 to + 30V

audible alarm: integrated - can be deactivated

LAN connection: RJ-45, 10Base-T or 100Base-TX connector

Communication protocol : WWW, ModbusTCP, SNMPv1, SOAP

Alarm protocols: E-mail (SMTP authentication is supported), SNMP Trap, Syslog

Configuration: T-Sensor, Telnet, keyboard

LCD screen operating temperature: Reading possible up to + 70 ° C, it is recommended to switch off the LCD screen above + 70 ° C

Supply : 9 to 30Vdc, consumption about 1W

Power cable : Coaxial, diameter 5,5 x 2,1 mm

Type of probe: Pt1000 / 3850, shielded cable maximum length 10 m

Dimensions: 136 x 160 x 45 mm (W x H x D)

Weight: about 340g

Warranty: 3 years 