Product features Room temperature sensor
DESCRIPTION AND APPLICATION
DECLARATION, CERTIFICATION, CALIBRATION
- The manufacturer provides an EU declaration of conformity .
- Calibration - The final metrological control - comparison with standards or working instruments - is carried out for all products. The continuity of standards and work measurement instruments is ensured within the meaning of article 5 of Law No. 505/1990 on metrology. The manufacturer offers the possibility of supplying the calibrated sensors in the laboratory (according to the requirements of EN ISO / IEC 17025) or in an accredited laboratory.
SENSOR INSTALLATION AND MAINTENANCE
The sensors are designed to be mounted on a wall or other horizontal surfaces. For fixing, it is necessary to prepare the required holes for mounting screws using a template (supplied with the sensor).
Before connecting the power cable, it is necessary to separate the perforated cover from the plastic base. Remove the cover and insert the cable through the 9mm hole, apply the base to the surface and screw with two screws or bolts. The length of the fixing bolts or screws for fastening should be selected depending on the thickness of the plastic base. Connect the power cable to the terminals according to the “Wiring” section.
"Diagram", place the perforated cover on the fixed base and lock it by clicking it. After installation and connection to the electrical measuring device, the sensor is ready for use. The sensor does not require any special care or maintenance. For a more detailed description of the installation, see the user manual of the sensor.
Sensor type | NS 100 | NS 101 | NS 102 | NS 300 | NS 301 |
Sensitive element type | Nor 1000/5000 | Nor 1000/6180 | Ni 891 | Nor 10000/5000 | Nor 10000/6180 |
Measuring range | LEXAN from -30 to 100 ° C | ||||
Maximum continuous current | 1 mA | 1mA | 1mA | 0.3 mA | 0.3 mA |
Sensor type | NS 103 | PTS 100 | PTS 200 | PTS 300 | HS 100 |
Sensitive element type | T1 = Ni 2226 | Point 100/3850 | Point 500/3850 | Point 1000/3850 | 20 kΩ NTC thermistor |
Measuring range | LEXAN from -30 to 100 ° C | ||||
Maximum continuous current | 0.7 mA | 2 mA | 1,2 mA | 0,8 mA | 1 mW *) |
*) maximum power consumption
Sensor type | NS 500 | NS 700 | Footnotes |
Sensitive element type | Point 1000/3850 | Point 1000/3850 | |
Output signal |
4 to 20 mA | 0 to 10 V | |
Measuring ranges | -30 ° C to 60 ° C 0 ° C to 35 ° C 0 ° C to 100 ° C 0 ° C to 150 ° C |
-30 ° C to 60 ° C 0 ° C to 35 ° C 0 ° C to 100 ° C 0 ° C to 150 ° C |
Ambient temperature around the connection head: -30 ° C to 70 ° C |
Food (Ucc) |
12 to 30 V DC | 15 to 30 V DC | Recommended value: NS 500: 12 V DC NS 700: 15 V DC |
Max. load resistance Rs |
150 Ω for 12 VDC power supply 700 Ω for 24 VDC power supply |
||
Rupture of the sensitive element | > 24 mA | > 10,5 V | |
Short sensitive element | <3.5 mA | ~0V |
**) Depending on customer requirements, it is possible to provide a custom measurement range from -40 to 150 ° C; the minimum range of the range must be 35 ° C (for example, -20 to 15 ° C; -30 to 80 ° C)
OTHER PARAMETERS | |
Precision class | Elements sensitive to Ni: class B, Δt = ± (0,4 + 0,007t), for t ≥ 0; Δt = ± (0,4 + 0,028 | t |), for t ≤ 0 in ° C; Elements sensitive to pt: class B according to EN 60751, Δt = ± (0,3 + 0,005 | t |) in ° C NTC 20 ° C kΩ: ± 1 ° C for the range from 0 ° C to 70 ° C |
Measurement error for NS 500 (range from -30 ° C to 70 ° C) |
power supply = 12 V: ± (0,5 ° C + 0,2% of range) power supply = 24 V: (-0,2 to 0,80 ° C) ± 0,2% of the range |
Measurement error for NS 700 (range from -30 ° C to 70 ° C) |
power supply = 15 V: ± (0,5 ° C + 0,2% of range) power supply = 24 V: (-0,2 to 0,80 ° C) ± 0,2% of the range |
Sensor connection | according to the wiring diagram |
Response time | τ 0,5 <8 s (in air flow 0,4 ms -1 ) |
Recommended wire section | 0,35 to 1,5 mm 2 |
Protection sign | IP 30 according to EN 60529 |
Connection head material | lexan |
Connection head dimensions |
71,9 x 59 x 27 mm |
Operating conditions | ambient temperature: -30 to 100 ° C without converter -30 to 70 ° C with converter relative humidity: max 85% (at room temperature 25 ° C) atmospheric pressure: 87 to 107 kPa |
Weight | 0.05 kg |
Please note: The manufacturer reserves the right to modify the design and technical characteristics of the products.