What is a MZ6 sensor ?
The MZ6 is a threshold PTC thermistor used as a thermal protection sensor in motors, transformers, and power systems.
Its resistance remains low and stable up to a specific switching temperature (typically between 60 °C and 180 °C, depending on the version), then increases sharply, indicating overheating.
It complies with DIN 44081 / 44082 standards, ensuring its interchangeability with other protection PTCs.
Operating principle
Under the nominal temperature (Tₙ), the resistance is low (about 150 Ω).
As soon as the temperature reaches the threshold, the resistance increases exponentially to several tens of kilo-ohms within a few degrees.
This transition is detected by a PTC control relay, which cuts off the control circuit to protect the system.
| Temperature (°C) | Typical resistance (Ω) |
| 20 | 150 |
| 80 | 160 |
| 100 | 170 |
| 120 (Tₙ) | 1650 |
| 140 | 4500 |
| 160 | 10 000 |
| 180 | 20 000 |
🧠 This sharp trigger curve makes it a reliable safety component for electromechanical systems.
Technical specifications
| Parameter | Typical value |
| Nominal resistance (Tₙ) | 60°C to 180°C depending on model |
| Resistance at 25 °C | 150 Ω ±20 % |
| Resistance to Tₙ | ≥ 1650 Ω |
| Maximum measurement current. | 2,5 mA |
| Electrical isolation | ≥ 2,5 kV |
| Response time | 3 to 5 s |
| Case | Epoxy, glass or ceramic |
Wiring Configuration
| Type | Description | Precision |
2-wire |
Series assembly in the detection circuit. | ✅ Standard |
Multiple chain |
Several MZ6 in series to monitor multiple engine zones. | 🏆 Industrial |
Integrated |
Stuck or molded in the motor winding. | 💡 Direct thermoprotection |
Self-heating
The measurement current being limited to a maximum of 2.5 mA, self-heating is negligible, ensuring purely external temperature detection.
Application areas
⚙️ Thermal protection of three-phase motors
🔋 Monitoring of transformers and power inductors
🚗 Battery protection systems and variable speed drives
🧱 Industrial applications compliant with DIN 44081/82
🧠 Sensors integrated into thermal cut-off relays