Radial temperature and humidity probe for duct - 4-20mA output
Reference: AR004967
Quantity | Unit price | You save |
---|---|---|
10 | 222,43 € | Up to €247,20 |
25 | 211,31 € | Up to €896,10 |
50 | 200,18 € | Up to €2 |
International shipping
Standard or express delivery
Secure Payments
All payments are secure and approved.
Best price guarantee
Contact us to define your payment method.
+33-233-611-670
English - French - German - Spanish
Product details about "Radial Duct Temperature and Humidity Probe - 4-20mA Output"
TECHNICAL DATA
Humidity, temperature transmitter.
Use Case exterior and interior.
Assembly on sheath.
Relative humidity, rod temperature sensors 150mm.
The measured values are also converted to another interpretation of humidity: dew point temperature, absolute humidity, specific humidity, mixing ratio, specific enthalpy.
INCLUDED IN DELIVERY
- T3113D
- Manual
- Traceable calibration certificate
- Free Tsensor configuration software
MEASURED VALUES
- Temperature
- Relative humidity
- Calculated values (dew point, etc.)
Temperature range : -30 to 125 ° C
Relative humidity range: 0 to 100%
Accuracy of the relative humidity measurement: ± 2,5% relative humidity from 5 to 95% at 23 ° C
Accuracy of temperature output: ± 0,4 ° C from -30 to + 100 ° C
± 0,4% from reading at + 100 ° C
Available temperature units: degrees Celsius, Fahrenheit
Dew point output accuracy and range - for details see graphs: ± 1,5 ° C at ambient temperature T <25 ° C and relative humidity> 30%
range -60 to +80 ° C
Accuracy and absolute humidity output range: ± 1,5 g / m3 at ambient temperature T <25 ° C
range from 0 to 400 g / m3
Accuracy and specific humidity output range: ± 2g / kg at ambient temperature T <35 ° C
range from 0 to 550 g / kg
Accuracy and output range of mixing ratio: ± 2g / kg at ambient temperature T <35 ° C
range from 0 to 995 g / kg
Precision and range of specific enthalpies: ± 3 kJ / kg at ambient temperature T <25 ° C
range: 0 to 995 kJ / kg
Housing operating temperature range with electronics: -30 to +80 ° C
LCD display operating temperature range: readable at an operating temperature of + 70 ° C, it is recommended to turn off the LCD screen above 70 ° C
Humidity sensor temperature compensation range: the entire temperature range
Current outputs - two-wire connection: 4-20mA, galvanically isolated with dual output models
Configuration of outputs and output range: user adjustable from PC
Filtering capacity of the sensor cover: 0.025mm - filter with stainless steel mesh
Housing protection with electronics: Electronics IP65, sensors IP40
Food: 9-30Vdc
Display dimensions: 88,5 x 95 x 195 mm (L x H x W), rod length 150 mm
Weight: about 225g
Warranty: 3 years
General
- Reference AR004967
- Name Radial temperature and humidity probe for duct - 4-20mA output
Features
- Measured Humidity
- Communication 4 ... 20mA
8 other products in the same category:


Temperature and humidity sensor with RS485 output

Duct mount temperature and humidity transmitter with RS485 output

Temperature and humidity sensor for ventilation duct - 4..20mA

Axial temperature and humidity probe for duct - 4-20mA output

Bar-type temperature and humidity probe with 4-20mA output

Axial temperature and humidity probe for duct with 0-10V output