Radial temperature and humidity probe for duct - 4-20mA output

Reference: AR004967

247,15 €
Quantity Unit price You save
10 222,43 € Up to €247,20
25 211,31 € Up to €896,10
50 200,18 € Up to €2
Radial temperature and humidity probe for duct - 4-20mA output
  • Temperature and humidity.
  • Exterior and interior.
  • Sheath mounting.
  • 150mm rod.
Delivery in 3 to 5 weeks

International shipping

Standard or express delivery

Secure Payments

All payments are secure and approved.

Best price guarantee

Contact us to define your payment method.

+33-233-611-670

English - French - German - Spanish

Product details about "Radial Duct Temperature and Humidity Probe - 4-20mA Output"

TECHNICAL DATA

Humidity, temperature transmitter.

Use Case exterior and interior.

Assembly on sheath.

Relative humidity, rod temperature sensors 150mm.

The measured values ​​are also converted to another interpretation of humidity: dew point temperature, absolute humidity, specific humidity, mixing ratio, specific enthalpy.

INCLUDED IN DELIVERY

  • T3113D
  • Manual
  • Traceable calibration certificate
  • Free Tsensor configuration software


MEASURED VALUES

- Temperature
- Relative humidity
- Calculated values ​​(dew point, etc.)

Temperature range : -30 to 125 ° C

Relative humidity range: 0 to 100%

Accuracy of the relative humidity measurement: ± 2,5% relative humidity from 5 to 95% at 23 ° C

Accuracy of temperature output: ± 0,4 ° C from -30 to + 100 ° C
± 0,4% from reading at + 100 ° C

Available temperature units: degrees Celsius, Fahrenheit

Dew point output accuracy and range - for details see graphs: ± 1,5 ° C at ambient temperature T <25 ° C and relative humidity> 30%
range -60 to +80 ° C

Accuracy and absolute humidity output range: ± 1,5 g / m3 at ambient temperature T <25 ° C
range from 0 to 400 g / m3

Accuracy and specific humidity output range: ± 2g / kg at ambient temperature T <35 ° C
range from 0 to 550 g / kg

Accuracy and output range of mixing ratio: ± 2g / kg at ambient temperature T <35 ° C
range from 0 to 995 g / kg

Precision and range of specific enthalpies: ± 3 kJ / kg at ambient temperature T <25 ° C
range: 0 to 995 kJ / kg

Housing operating temperature range with electronics: -30 to +80 ° C

LCD display operating temperature range: readable at an operating temperature of + 70 ° C, it is recommended to turn off the LCD screen above 70 ° C

Humidity sensor temperature compensation range: the entire temperature range

Current outputs - two-wire connection: 4-20mA, galvanically isolated with dual output models

Configuration of outputs and output range: user adjustable from PC

Filtering capacity of the sensor cover: 0.025mm - filter with stainless steel mesh

Housing protection with electronics: Electronics IP65, sensors IP40

Food: 9-30Vdc

Display dimensions: 88,5 x 95 x 195 mm (L x H x W), rod length 150 mm

Weight: about 225g

Warranty: 3 years

General

  • Reference AR004967
  • Name Radial temperature and humidity probe for duct - 4-20mA output

Features

  • Measured Humidity
  • Communication 4 ... 20mA

Attachments

Radial Duct Temperature and Humidity Probe - 4-20mA Output - Quick Start
AR006568 / AR003830 / AR006569 / AR004967 / AR006570 / AR004384 / AR006065 / AR005133 / AR006571 / AR006572 / AR006573 / AR004740 / AR004732 / AR006574
Download (2.25MB)
Radial Duct Temperature and Humidity Probe - 4-20mA Output - Introduction Manual
AR006569 / AR004967 / AR004303 / AR006570
Download (4.24MB)

8 other products in the same category: