Intrinsically safe humidity and temperature transmitter with cable probe, 4-20mA output

AR004611
302,78 €
1 to 3 weeks
  • Probe on 1m cable.
  • Temperature and humidity.
  • potentially explosive areas.
  • ATEX certification.

Volume reductions

Quantity Hand off You save
10 10.0007% Up to € 302,80
25 14.499% Up to € 1
50 19.0006% Up to € 2
Quantity

Secure Payments

All payments are secure and approved.

Best price guarantee

Contact us to define your payment term.

+33-233-611-670

English - French - German - Spanish

International shipping

EXPRESS OR STANDARD delivery.

TECHNICAL DATA

ATEX certified transmitter temperature and humidity.

For use in potentially explosive areas.

Relative humidity and temperature transmitter with remote probe on 1 meter cable.

The measured values ​​are also converted to another interpretation of humidity: dew point temperature, absolute humidity, specific humidity, ratio of mixtures, specific enthalpy.

ATEX certification for use in explosive atmospheres. 

INCLUDED IN DELIVERY

  • AR004611
  • Manual
  • Traceable calibration certificate
  • Free Tsensor configuration software


MEASURED VALUES

- Temperature
- Relative humidity
- Calculated values ​​(dew point, etc.)

Relative humidity range: 0 to 100%

Relative humidity measurement uncertainty: ± 2.5% relative humidity from 5 to 95% at 23 ° C

Temperature measurement uncertainty: ± 0.4 ° C from -30 to + 100 ° C
± 0.4% of reading above + 100 ° C

Available units: degrees Celsius, Fahrenheit

Uncertainty and dew point measurement range: ± 1.5 ° C at ambient temperature T <25 ° C and RH> 30%
Range -60 to +80 ° C

Uncertainty and absolute humidity range: ± 1.5g / m3 at ambient temperature T <25 ° C
Range 0 to 400 g / m3

Uncertainty and specific enthalpy range: ± 2g / kg at ambient temperature T <35 ° C
Range 0 to 550 g / kg

Uncertainty and range of the mixture ratio: ± 2g / kg at ambient temperature T <35 ° C
Range 0 to 995 g / kg

Uncertainty and specific enthalpy range: ± 3kJ / kg at ambient temperature T <25 ° C
Range 0 to 995 kJ / kg

Housing operating temperature: -30 to + 60 ° C

Max ambient temperature of the housing: max + 60 ° C

LCD display operating temperature: Reading possible at + 70 ° C, it is recommended to switch off above 70 ° C

Relative humidity sensor temperature compensation: the whole beach

Current output - 2 wires: 4-20mA, galvanically isolated

Output configurations and output ranges: Adjustable by user

Protection filter: 0.025mm - Filter with stainless steel mesh

IP protection index: IP65 electronic, IP40 sensor

Supply : 9-30Vdc

Cable length: 1m, 2m or 4m optional

Display dimensions: 88.5 x 114 x 39.5 mm (W x H x D), probe length 88 mm, probe diameter 18 mm

Weight: About 210g, 1m of cable

Warranty: 3 years 

AR004611

Information

Measured
Pressure
Communication
4 ... 20mA
Related products (2 other products in the same category)