Europe: +33 2 33 61 16 70 | America: +1 438 800 6104

IP65 contact temperature probe

Reference G03.10

Delivery in 3 to 5 weeks
  • Resistance sensors.
  • For piping.
  • Measures contact surface temperature.
  • The sensitive element can be isolated.
319.55KB Download

Datasheet G03.10 | Contact temperature sensor IP65

Product features IP65 contact temperature probe

Description and application

These resistance sensors are intended for measuring the contact surface temperature. the available sensors, including fastening strap, are suitable for temperature measurement on the pipes.

The dimensions of the sensor allow the sensor to be placed even under the pipe insulation. The standard operating temperature range is between -50 and 130 ° C.

The sensitive element is constructed to be isolated from ambient influence. The sensors can be used for any compatible control system with the sensing element output signals or the output signals shown in the sensing element type table.

Contact temperature probe

Accessories

  • heat conductive paste up to 200 ° C, 5g

DECLARATION, CERTIFICATION, CALIBRATION

  • The manufacturer provides an EU declaration of conformity.
  • Calibration - The final metrological control - comparison with standards or working instruments - is carried out for all products. The continuity of working standards and measuring instruments is ensured within the meaning of Article 5 of Law No. 505/1990 on metrology. We offer the possibility to supply the calibrated sensors (according to the requirements of EN ISO / IEC 17025) or in an accredited laboratory.  

Sensitive element type
Nor 1000/5000 Nor 1000/6180 Ni 891 Nor 10000/5000 Nor 10000/6180
Measuring range
-50 to 130 ° C
Maximum continuous current
1 mA 1 mA 1 mA 0.3 mA 0.3 mA

Sensitive element type
T1 = Ni 2226 Point 100/3850 Point 500/3850 Point 1000/3850 20 kΩ NTC thermistor
Measuring range
-50 to 130 ° C
Maximum continuous current
0.7 mA 3 mA 1.5 mA 1 mA 10 mW *)

*) maximum power consumption

OTHER PARAMETERS
Accuracy class **) Elements sensitive to Ni: class B, Δt = ± (0,4 + 0,007t), for t ≥ 0; Δt = ± (0,4 + 0,028 | t |), for t ≤ 0 in ° C 
Sensitive elements of Pt: B according to EN 60751, Δt = ± (0,3 + 0,005 | t |) in ° C 
NTC 20 kΩ: ± 1 ° C for the range 0 to 70 ° C
Sensor connection
according to the wiring diagram
Response time
sensor type S150A τ 0,5 ≤ 10s, τ 0,9 ≤ 45 s (on the smooth surface without paste)
Isolation resistance
> 200 MΩ at 500 V DC, 25 ° ± 3 ° C; humidity <85%
Protection sign
IP 65 according to EN 60529
Protective tube material
brass
Input cable shielded silicone 2 x 0,22 mm 2 
shielded silicone 4 x 0,15 mm 2
Standard cable length
2, 5, 10
Plastic protection material
POLYAMIDE type S150A
Standard collar length
40 cm
Minimum pipe diameter
20 mm
Working conditions
ambient temperature: -50 to 130 ° C 
relative humidity: max. 100% (at room temperature 25 ° C) 
atmospheric pressure: 70 to 107 kPa
Weight about 0,15 kg

**) Regulated by immersing the sensor in a liquid, no method error is taken into account - influence of the ambient temperature and the environment, uneven surface, etc. In terms of two connections, the impact of wire resistance be added. At a temperature of 20 ° C, the impact of lead resistance is 0,4 ° C / 1 m.

These products can interest you